This paper addresses the experimental characterization of a base-isolation system for the seismic qualification, of High Voltage (HV) ceramic circuit breakers, in accordance with the European standard CEI EN 62271-207. The adopted solution is based on an innovative application of wire rope isolators. The results of a preliminary investigation of an HV circuit breaker, which was base-isolated with Wire Ropes, were previously illustrated in a companion paper in which the effectiveness of this isolation system was analytically demonstrated. To validate these results, a shake table test campaign has been performed that includes the performance analysis of two optimal isolation system configurations. The results, which are illustrated in this paper, show both the effectiveness of this isolation system and the reliability of the proposed FE model.

Alessandri, S., Giannini, R., Paolacci, F., Amoretti, M., Freddo, A. (2015). Seismic retrofitting of a HV circuit breaker through base isolation with steel cable dampers. Part 2: Shaking table tests validation. ENGINEERING STRUCTURES, 98, 263-274 [10.1016/j.engstruct.2015.03.031].

Seismic retrofitting of a HV circuit breaker through base isolation with steel cable dampers. Part 2: Shaking table tests validation

Alessandri S;PAOLACCI, Fabrizio
;
2015-01-01

Abstract

This paper addresses the experimental characterization of a base-isolation system for the seismic qualification, of High Voltage (HV) ceramic circuit breakers, in accordance with the European standard CEI EN 62271-207. The adopted solution is based on an innovative application of wire rope isolators. The results of a preliminary investigation of an HV circuit breaker, which was base-isolated with Wire Ropes, were previously illustrated in a companion paper in which the effectiveness of this isolation system was analytically demonstrated. To validate these results, a shake table test campaign has been performed that includes the performance analysis of two optimal isolation system configurations. The results, which are illustrated in this paper, show both the effectiveness of this isolation system and the reliability of the proposed FE model.
2015
Alessandri, S., Giannini, R., Paolacci, F., Amoretti, M., Freddo, A. (2015). Seismic retrofitting of a HV circuit breaker through base isolation with steel cable dampers. Part 2: Shaking table tests validation. ENGINEERING STRUCTURES, 98, 263-274 [10.1016/j.engstruct.2015.03.031].
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11590/140050
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 69
  • ???jsp.display-item.citation.isi??? 50
social impact