This paper briefly describes the design and characterization of a base isolation system that protects HV ceramic circuit breakers during seismic events. This qualifies them to the European standard CEI EN 62271-207. The solution is based on an innovative application of wire rope isolators. Preliminary numerical analyses and tests were performed on a typical HV circuit breaker and demonstrated the effectiveness of the proposed isolation system in reducing seismic demand. The results were also validated using a shaking table, which is described in an accompanying paper. The on-site installation of this system in several Italian substations has finally proved simple enough to upgrade the equipment for seismic protection.

Alessandri, S., Giannini, R., Paolacci, F., Malena, M. (2015). Seismic retrofitting of a HV circuit breaker through base isolation with steel cable dampers. Part 1: Preliminary tests and analyses. ENGINEERING STRUCTURES, 98, 251-262 [10.1016/j.engstruct.2015.03.032].

Seismic retrofitting of a HV circuit breaker through base isolation with steel cable dampers. Part 1: Preliminary tests and analyses

Alessandri S;PAOLACCI, Fabrizio
;
Malena M.
2015-01-01

Abstract

This paper briefly describes the design and characterization of a base isolation system that protects HV ceramic circuit breakers during seismic events. This qualifies them to the European standard CEI EN 62271-207. The solution is based on an innovative application of wire rope isolators. Preliminary numerical analyses and tests were performed on a typical HV circuit breaker and demonstrated the effectiveness of the proposed isolation system in reducing seismic demand. The results were also validated using a shaking table, which is described in an accompanying paper. The on-site installation of this system in several Italian substations has finally proved simple enough to upgrade the equipment for seismic protection.
2015
Alessandri, S., Giannini, R., Paolacci, F., Malena, M. (2015). Seismic retrofitting of a HV circuit breaker through base isolation with steel cable dampers. Part 1: Preliminary tests and analyses. ENGINEERING STRUCTURES, 98, 251-262 [10.1016/j.engstruct.2015.03.032].
File in questo prodotto:
File Dimensione Formato  
1-s2.0-S0141029615001753-main.pdf

accesso aperto

Tipologia: Versione Editoriale (PDF)
Licenza: DRM non definito
Dimensione 4.64 MB
Formato Adobe PDF
4.64 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11590/141769
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 85
  • ???jsp.display-item.citation.isi??? 60
social impact